Skip to main content

The T 97 underground station if space is limited

Tight for space? Due to the extremely compact design of the T 97 underground station, most projects can still be implemented. 

 

The prefabricated underground station T 97 compliant with SN EN 62271 202. The unit can be operated from outside and has a very shallow design

The special features of the T 97 are its extremely low structure height of little more than one metre and the hinged metal roof.

The station is used with the roof open, whilst the technician stands on a false floor, which is approx. 60 cm below ground level. 

The design complies with the latest state-of-the-art technology and meets the requirements of the applicable regulations and technical standards, namely the type test standard SN EN 62271-202 for prefabricated transformer stations. 

Since the interior fittings are installed and the routine testing takes place at the Villmergen factory, the station can be assembled on-site in one day.

T 97 underground station

Tiefstation T97

The industrially prefabricated building station can be operated from the outside

The T 97, made by Betonbau GmbH und Co. KG, Germany, is a prefabricated compact building station in concrete cabin design. It is an extremely low structure, measuring just over 1 m high and can be used outdoors.

A hinged metal access hatch allows access via stairs to a service floor 40 to 60 cm below ground level.

The stations are fully fitted in our factory, transported by us to the construction site, and installed the same day.

The concrete housing is seamless and comes as a single piece.

Layout and sizes are variable to a certain extent.

The T 97 station model fully complies with the requirements of the Ordinance on Heavy Current Installations and relevant engineering standards, namely SN EN 62271-202 for prefabricated stations utilising high voltage and/or low voltage.

The T 97 station model fully complies with the requirements of the Ordinance on Heavy Current Installations and relevant engineering standards, namely SN EN 62271-202 for prefabricated stations utilising high voltage and/or low voltage.

 

 

Product features

Installation
free-standing (standard), slope installation, installation on in-situ concrete, other options

Operating temperature
outdoors -40 °C to 35 °C / indoors -5 °C to 45 °C

Type testing
SN EN 62271-202 incl. Internal Arc Classification IAC AB 20 kA (1 s) with all MV switchgear types

Standard façade surface
Synthetic resin plaster, colour of your choice, opening hatch made of stainless sheet steel, textured
Foundation: Bitumen protective coating, black, Ilack C 

Concrete quality
• Reinforced concrete, C35/45, XC4, XA1, XF1 compliant with SN EN 206-1
• Fire resistance class: REI 60
• proven oil tightness compliant with VSE 2.19 d

Interior paint
entire interior painted with white water-based dispersion

False floor
Consisting of an aluminium frame to which pressure-proof, phenolic resin-coated plywood panels are bolted. The surface of these panels is slip-resistant, and moisture resistant

Oil collecting sump
oil-tight concrete structure, with optional additional oil-tight coating for protection zone S3, compliant with VSE 2.19 d

Lifting equipment
four lifting points are recessed on the foundation's exterior

Cable entries
Entry system, quantity, size and position according to customer specifications

Construction power entry
Ø 90 mm, with aluminium cover (position according to customer specifications)

Earthing system
consisting of an all-round main earth line made of Cu Ø 8 or Ø 10 mm and earthing busbar

Earth cable feedthroughs
two feedthroughs are located on the diagonally opposite walls of the cable duct and are connected to the concrete reinforcement bars, optional isolated feedthroughs and earthing points on one side

Station accessories
wide range of options and equipment available

Any questions?